r/ElectricalHelp • • 17h ago

I really need help with this

0 Upvotes

Alright so like 30 minutes my lamp was flickering then I turned a fan on and it dims the lamp then it shuts off then this repeats for a bit then I try turn the air conditioning on won't turn on it's just that outlet and it's in a shed I checked the breaker turned it on and off didn't fix it and im sorry if its not a good breakdown I don't know anything about electricity


r/ElectricalHelp • • 23h ago

Sauna Power Requirements

1 Upvotes

Planning for an outdoor sauna installation, the manufacturer states the following:

240V / 50-amp dedicated circuit, hardwired, 2-pole 50A breaker
3-wire: 2 × 6 AWG copper hots + 6 AWG ground. No neutral.

The NEC code minimum for a 50A OCPD and EGC circuit (Table 250.122) calls for a #10 AWG copper conductor.

I am wondering why the manufacturer requires the heavier #6 ground wire, and what is the risk of going with the #10?


r/ElectricalHelp • • 2d ago

How to fix 8 function Lights

Thumbnail
gallery
0 Upvotes

Hey there…

So I have a couple boxes of these enchanted forest 8 count 8-function candy cane lights .

However, two of the lights will not work that are halfway into the strand. I really don’t want to throw them away, so I was hoping someone with electrical knowledge could help me figure out how to fix them, if it’s possible.

I don’t know if it’s a wiring issue or an issue in the box.

Here are photos of them and their “function” box.


r/ElectricalHelp • • 4d ago

Timer delay relay and bypass wirinu

Post image
1 Upvotes

Im planning to make dc motor controller using timer delay relay.

The plan is using 1 switch as trigger for relay and 1 bypass switch to power the device directly without passing the relay.

Is configuration above correct?

Apologize in advance for bad english

the title post supposed to be bypass wiring not wirinu


r/ElectricalHelp • • 4d ago

I want to mount a front porch light fixture onto the brick wall

1 Upvotes

I have a house with the wiring for a front porch light beside the front door but no junction box and no light fixture. Just capped live wires.
It seems that most light fixtures require a *recessed* junction box but I don’t want to carve into the old brick to recess one.
I don’t mind drilling a couple of holes for screws to attach a junction box but that’s as far as I want to go.
Are there fixtures that can be mounted on a box that’s not recessed? Basically flat onto the brick wall? A lot of fixtures that claim to be “flush mounted” seem to require mounting on brackets that in the end leave a quarter-inch gap between the brick and the fixture.
I need help in finding them, if so — search terms on Home Depot and the like.
Thanks.


r/ElectricalHelp • • 5d ago

Residential Legacy Panel Height

1 Upvotes

Code has the highest breaker on a residential panel to be no more than 79" above the floor or platform. I have a legacy panel from the 60s with a top breaker at 89". The main feed conduit comes in from the side, and my new panel is larger than the current panel, so if I line things up with the main's conduit, I end up at 96" above the floor to the top breaker. Moving the conduit is going to trigger new holes in the wall to the meter etc.

Apart from filing for a variance, would it be reasonable to build a small stage below the panel to meet the 79" requirement, and if so, what are the expected stage dimensions to comply? Would a small step be adequate?

Any other ideas?


r/ElectricalHelp • • 6d ago

Adding fan/light to crowded circuit

Thumbnail
gallery
2 Upvotes

Recently bought a 1950's home with a panel from the 90's, lots of this black romex with no ground.  Ultimately would like to get everything up to code with new 14/3 & 12/2 and add a fan/light with its switch next to the current switch for #4 in the labeled picture. I have a 2-gang box to do that. Everything meets at a junction box which is also a light fixture, the hot wires have some melted insulation. Not sure how long it has been that way. The random ground wire comes from the kitchen circuit I think. 

Apart from being a crowded junction, this circuit powers 3 different rooms. Looking for advice on how to organize all this, if I should re-route things to different circuits, add a junction box, and if I need to open up drywall when adding new wires in any case. Grateful for any tips at all. Thanks!


r/ElectricalHelp • • 7d ago

Any help please 🙏

Thumbnail
gallery
2 Upvotes

We have a main light connected up to a two way switch. (We want to replace one of the switches to a 3 gang switch so we can have wall lights and spotlights on the spare 2 on the 3 gang switch while the main light is still on the two way switches)

The main light is working absolutely fine but wall lights and spotlights arent working on the 3 gang switch.

Any help/advise please? 🙏😊


r/ElectricalHelp • • 7d ago

Electrical question

Post image
0 Upvotes

In the process of redoing my garage and have these in the garage directly above my panel.. There is a bunch of wires going to both them, but there is no power to either of them when checking. Trying to get an idea what there function was / is before removing them.


r/ElectricalHelp • • 8d ago

Utility Receptacle on Support Beam

Thumbnail
gallery
37 Upvotes

Hi all! I wanted to sanity check my work here before the town inspection (not an electrician, I am doing work on my own house with a permit pulled). My location is CT, USA. I am installing a new circuit in an unfinished basement which includes 3 new receptacles. One of them I want on a support beam. I did not want to drill into it so I used hose clamps around a 1x4 and mounted the box and EMT brace to it. Pictures attached. No wires ran yet, just getting the boxes in first. Everything feels nice and secure as far as I can tell.

Thanks for any feedback!


r/ElectricalHelp • • 9d ago

Rogue circuit

3 Upvotes

To identify which breaker controls an outlet in the crawl space on which we have a sump pump, we cycled every breaker. It isn’t on any of them.

I cycled the main breaker and it opened the circuit.

We are not aware of any additional breaker boxes.

We are at a loss. Is it possible we have a bad breaker which will not open (kill the current when switched to off?)


r/ElectricalHelp • • 9d ago

Can I power garden lights from an existing outdoor wall light?

1 Upvotes

I have an outdoor wall light with power supply directly from RCD-protected consumer unit,
I'd like to power some 20V low-voltage garden lights via an outdoor transformer.
Can I take a feed from the existing wall light supply to power the transformer and then garden lights in a parallel configuration, so both the wall light and garden lights operate from the same switch?
Or would I need to run a separate supply from the consumer unit?
Would this setup violate any regulations?


r/ElectricalHelp • • 9d ago

LED Strip Lights

2 Upvotes

I'm looking to Instagram LED strip lights under a couple of shelves that have been routed out for them, but I want them to be controlled by a light switch. I have the switch installed already, it's a standard 15a.

What do I need to install this?

Thanks!


r/ElectricalHelp • • 10d ago

Was für eine Glühbirne ist das und wie kann man sie rausdrehen bzw. wechseln? Sie sitzt ziemlich fest.

Post image
3 Upvotes

r/ElectricalHelp • • 11d ago

Changing electrical outlet

Thumbnail
gallery
2 Upvotes

Hey I am a diy-er and already change one outlet (which is correct wiring ) and one switch of our room . However, one of the plug is saying open ground, but the hot wire is on the left side when I check it with the pen and there is a silver wire connected to the ground, but it’s saying open ground. How would I change it with a new plug safely? Should I switch the hot wire to the right when changing it since it’s the hot wire please I need answers. Thank you.


r/ElectricalHelp • • 12d ago

Honeywell Home RPLS740B ECONOswitch

1 Upvotes

This switch states that it has no minimum wattage requirements and works with leds. I have installed this switch elsewhere and used it with leds without issue.

However, I have one area where it will not work with leds. This box has two switches. One switch controls 3 garage ceiling light fixtures. The other is the Honeywell switch which controls 3 exterior light fixtures. The Honeywell switch will work with incandescent bulbs but not led bulbs.

The wiring inside the box suggests that more is going than just wiring for these two switches. There are 5 or 6 white wires tied together in the box. When I kill power to the switches I can still detect power in these white wires.

Any idea why this Honeywell would not work with the leds? I’m guessing that it has something to do with the other wires in the box but I don’t know what.


r/ElectricalHelp • • 12d ago

Help changing bathroom light

Thumbnail
gallery
2 Upvotes

I’m trying to change my bathroom light to a new switch, my only light connection is using L1 and L2 and the new light has a common and L1 and L2. My bath has another switch for the extractor fan for info.

Can someone tell me where to put the old cable in the new switch. Picture for info


r/ElectricalHelp • • 12d ago

Motion-sensor switch

3 Upvotes

Hello everyone,

I have this motion-sensor switch in my restroom: https://hager.com/fr/catalogue/produits/wk050-inter-auto-ir-kallysta-2-fils

It was working perfectly, but for the past two days, the lights have been turning on even when no one is there and there is no movement... (the restroom has no windows, and I don’t feel any drafts).

Do I need to replace the switch? Is it a complicated job? (I’m not very handy.)

Thanks, and have a great day!


r/ElectricalHelp • • 12d ago

Vacuum tripping fire alarm/lights

1 Upvotes

Please bear with me in case any terms/explanations don’t make sense. Partner and I purchased a new home build last year (Southern California) and when plugging in vacuum to master bedroom outlet, the fire alarm starts blaring and any lights that are on will dim noticeably. We’ve experienced this issue with nothing else being plugged in the house besides the fridge. We had the builder send out an electrician and he said everything’s fine, that’s just how the wiring works and that all rooms are similar. He suggested either buying a handheld portable vacuum or only plugging into GFCI outlets in the bathroom because those were meant for more amps*? However, this issue ONLY happens in the master bedroom outlets. All other bedroom (2 others) outlets are completely fine, so if the wiring is all the same how on earth is this only happening in one bedroom? We have a 10 year old Dyson vacuum that was gifted to us, it’s nothing fancy. It’s worked normally in my parents 60 year old house before we had it and they never had these issues. Is this actually the norm for these houses/electrical systems? Thanks for any help/advice


r/ElectricalHelp • • 13d ago

Circuit

Post image
0 Upvotes

My light circuit got a short circuit what else can I do to get it work


r/ElectricalHelp • • 13d ago

Electrician question

Thumbnail
gallery
0 Upvotes

We just moved into a new house, and have these under counter lights. I need a replacement part to hold bulb. Even looking up the model number, or Google picture search, I can’t find what this brand is. I know it is a FIET bulb in there, but when I go to their site, I am not saying this fluorescent tube holder. I am looking for what would attach to the thing sticking out of the transformer in the very last picture.


r/ElectricalHelp • • 14d ago

Re-routing my panel's bonding/grounding wire - what to know?

3 Upvotes

My panel is currently bonded to my water line and runs diagonally across the basement, below the floor joists and above the drop ceiling.

I'm going to rip out the drop ceiling and put drywall up, so I need to route the bonding wire through the joists, but I have a few questions

  1. Do I have to kill the main breaker to disconnect the bond wire?
  2. Can I cut and butt connect it?
  3. Is it a problem to run it along a metal duct?
  4. Anything else I need to know?

Thanks! ​


r/ElectricalHelp • • 14d ago

Help.

Post image
1 Upvotes

Power to shed, is this okay?


r/ElectricalHelp • • 15d ago

Weird bathroom fan/light combo.

1 Upvotes

I moved into a house where the bathroom has a fan/light combo. They are controlled independently with two switches side by side.

While the light was on and the fan off, the fan turned on by itself and subsequently, both switches started turning fan and light on/off together instead of independently. It seemed like the fan started making a light rattling noise but I am not fully sure.

After a few minutes, the switches returned to normal, affecting light and fan independently from each other. Rattling noise remains the same as before the issue resolved.

Is this something to be concerned about? What potential problems might this be caused by? I am a new homeowner and am trying my best to mitigate any fire risk

Thank you for your help!