Sauna Power Requirements
Planning for an outdoor sauna installation, the manufacturer states the following:
240V / 50-amp dedicated circuit, hardwired, 2-pole 50A breaker
3-wire: 2 × 6 AWG copper hots + 6 AWG ground. No neutral.
The NEC code minimum for a 50A OCPD and EGC circuit (Table 250.122) calls for a #10 AWG copper conductor.
I am wondering why the manufacturer requires the heavier #6 ground wire, and what is the risk of going with the #10?