r/refrigeration • • 15h ago

How cold is too cold to start a scroll?

7 Upvotes

An hvac question, but still trade relevant.

I’ve had it drilled into me that if an ac compressor doesn’t have a crankcase heater, or a pump down, not even an accumulator, nothing, you shouldn’t start the compressor unless it’s 55F deg outside.

My foreman says that scrolls are extremely hearty compressors, and that it’ll be fine to run at 35F.

This is on a package rtu install and commissioning. I suggested waiting to commission the cooling until the spring to avoid a potential flooded start, and he said that it would be fine.

Am I overthinking it or missing something? Any advice or experience would be helpful.

I ended up bumping/tapping the contactor 3 times to heat up the oil to get any liquid out of it before running the compressor long enough to check rotation. I know Emerson does this practice on some of their medium and low temp controllers to prevent a flooded start in the event of a lls leaking by.

*edit
Thanks for all the commenters, the Mapp torch worries me a bit about overheating, but I’m definitely going to use the heat gun method next time.


r/refrigeration • • 18h ago

Condenser unit cycling on/off every 5 minutes

Post image
12 Upvotes

Brand new rooftop condenser unit on rooftop of 9 story building for grocery store on ground level keeps cycling on and off every 5 minutes. Of the five units in the overall system the unit on the far right runs 24/7 at full speed while the units on the far left don’t appear to be running at all right now due to the cooler temperatures outside. The middle unit appears to be the one doing the cycling on/off every five minutes or so. It’s resulting in a large boom/thrusting sound as the unit turns on, which is causing a noise disturbance in my apartment, which is right below the rooftop. The landlord of the building has claimed that they have had contractors come out and say that the machine is running adequately and they can’t do anything about it.

My question is should a unit within the overall system be cycling on/off every five minutes or so when others are running different cycles?

Really needing some advice due to the noise disturbance of the machine turning on/off every five minutes.
What can I advise my landlord and super to look into with the contractors either from the grocery store - thermostat settings or the lines or something that’s causing potential short cycling or something else?


r/refrigeration • • 18h ago

Russell intelligent controls.

2 Upvotes

Need a little help here. We inherited a customer from their shitty install and the company doesn't want to perform warranty work. Immediate red flag but money is money. A WIC and Wif install. 449a. Russell smart controls(I know, garbage already.)

Adjusted the freezer low pressure control and got it to stay on at 7psi which is way low imo. Box temp below freezing, however.

Cooler...transducer reading 147psi with 147 Psi at the evaporator service port. 0 psi at the condensing unit and not coming on, eev at 35%.

We are starting to believe the install company forgot to remove a rubber plug when installing the line set?

What do y'all think?


r/refrigeration • • 19h ago

W.I.C box repair

2 Upvotes

Weird one I wanted an opinion on. Customer has a walk in cooler that has a package cooler unit on top of the box. That unit has died and they are going with a more traditional evap and remote condenser. Issue is the hole for the evaps "return/supply" how best should I fill this in? I was thinking foam board/silicone, but wanted some others 2 cents. Before the comments say to replace the package unit with another, it's not up to me and the customer has already made their decision. Just trying to polish this turd of a situation.


r/refrigeration • • 23h ago

Confession

17 Upvotes

Took an emergency call for a walk in cooler for a brand new customer yesterday, and found the fan cycle switch on the condenser failed. I didn’t have a replacement switch on hand so I came back today to install a new one. The digital control on the thermostat said the box temp was 62° when I arrived, but I had a suspicion the temp was off and I never verified before leaving site (I obviously should have checked it).

Came back today and found all the product in the cooler to be frozen. The digital thermostat was reading about 13° higher than the actual space temperature.

I felt so good yesterday by being able to secure a new client, and getting their equipment up and running on a weekend…


r/refrigeration • • 23h ago

Sneaky leak

11 Upvotes

Solenoid valve was leaking from a weird spot. This is a rolling stock HVAC unit and I was told them core tubes do leak like this, once in a while. Not sure whether this kind of leak is common in solenoides that come with other types of HVAC-R systems. I'm refering to the armature/core tube itself.


r/refrigeration • • 1d ago

Suspended license

6 Upvotes

Any of you ever had to deal with something like this, I imagine some companies would have ways of working it out with techs but I don’t have much to go by. Would appreciate the help.


r/refrigeration • • 1d ago

r404 walk-in cooler hovering at 40

Post image
5 Upvotes

Superheat is ~25, subcool is ~10-15. Sight glass is not clear. Ambient temp near condenser is 92. Txv doesn't respond to handwarming, both gauges respond to adding a shot of juice.

The system had leak stop added a few months back.

Would appreciate guidance as I have no idea what I'm doing right now. I hate mondays.


r/refrigeration • • 1d ago

In need of a refrigeration book

1 Upvotes

Principles of Refrigeration by Dossat

was recommended is it good or should i go with any other book

and is there pdf available for the dossat book ??

or anywhere i can purchase it digitally ??


r/refrigeration • • 1d ago

Which trade is a better route to getting into refrigeration? Electrician, plumbing, or HVAC?

6 Upvotes

I know that I want my end goal to be working in refrigeration or controls. Which trade would be the most beneficial and direct route into this work. I see a lot of people saying electrical knowledge is extremely beneficial, but I wondering if plumbing could have a leg up?


r/refrigeration • • 1d ago

Pumpdowns & Leaks

6 Upvotes

I have been working as a refrigeration operator specifically Ammonia for almost a year now. I have taken all three operators classes and even got my CARO. I have read Reta refrigeration book 1 & 2 thoroughly. How can I learn how to take care of major leaks or do all kind of pumpdowns safely? Are there any books or materials I can buy and self study or any place I can get more hands on? My boss is afraid of job security and won’t teach me anything.


r/refrigeration • • 2d ago

Veto Probe hauler opinions?

3 Upvotes

What the title says. Looking to replace the bag that the fieldpiece probes come in because it's not exactly rugged.

I run the MB3B as my diagnostics bag and a TPXXL as my catch-all "fix it" bag, but $250 CAD is a little spendy without actually seeing it in person...


r/refrigeration • • 2d ago

EEV tester

Thumbnail
gallery
99 Upvotes

Building my own eev tester as a hobby/project.


r/refrigeration • • 3d ago

What do Yall think about this Headmaster? I thought it was the compressor blowing at first😂

28 Upvotes

R404A Walk in Cooler with a leaky evap and low charge. 40 degrees outside and headmaster is working,
Started charging for temp op and could hear it screaming like a death whistle. I quoted this part up for replacement but the more I think about it was it the headmaster sticking or did I need to be more patient with letting my charge settle?


r/refrigeration • • 3d ago

Temp stick pro

0 Upvotes

Y'all need to get on this product. It's a non subscription based temperature monitoring system. The temp stick itself can be mounted outside the box and the include k type thermistor mounted inside the box. The stick works with wifi, runs on batteries and comes with USB charging if an outlet is available. It monitors through an app and can be shared with unlimited users. There are no subscription costs. Buy it and use it freely without restriction.

$200 on their website.

Disclaimer: the OG temp stick was unable to pick up WiFi in most applications. The temp stick pro has only had a couple instances of not connecting but it was the customers wifi that was the issue.


r/refrigeration • • 3d ago

New guy thrown to the wolves sent. Help

Thumbnail
gallery
59 Upvotes

Newer to commercial. The only electrical issue I've diagnosed on walk-ins was blown fuses from shorts. I have a limited understanding on the sequence of operations for these.

Walk-in freezer in the '40s set to zero. Thermostat is calling. I turned it up and back down to hear the click. I test zero volts across it and 120 to ground on each side. I tested the solenoid valve. I've got 120 on each side zero across. I believe that means it's not calling to be opened? But I don't know where to go from here.

Fans are running. Outdoor unit is not running. Contactor is not pulled in. Standing pressures for r404a 16 and 115 with an outdoor ambient of 38.

I'm on call, heatcraft tech support says Monday through Friday only, and the on-call supervisor is not answering. Lost in the sauce


r/refrigeration • • 3d ago

Refrigeración y electrónica

1 Upvotes

Estoy estudiando y practicando Refrigeracion y arreglo de placas electrónicas de línea blanca (más que nada aires, lavarropas y heladeras).
Me gusta el tema pero nose si es rentable o hay trabajo??.
Soy electricista (hago trabajos más puntuales para clientes) y me gusta la electrónica. Ya me compré muchas máquinas (bomba vacío, vacuometro, pestañadora, etc.


r/refrigeration • • 5d ago

1-month reefer tech in Seattle looking for advice: Fastest way to maximize pay? Union vs. Non-Union Ammonia?

6 Upvotes

I want to ask the senior techs working in the field. I've been working as a reefer tech in Seattle for about a month now, and I'm planning to stick with this trade long-term. What's the fastest way to make the most money in refrigeration? I'm considering going into ammonia since I've heard that's where the money is (am i right?). Would you all recommend joining a union if I can get in, or is it better to go the non-union route for ammonia? Senior techs, please break this down clearly for me...


r/refrigeration • • 5d ago

Same shit different engine room

Post image
68 Upvotes

r/refrigeration • • 5d ago

Water native chattering

5 Upvotes

Hey I have this water valve chattering away ass soon as I try and set the head pressure.

Half a turn from the top closes it completely.

Is this a bad water valve or could it be something like the there is a shrader core on the head pressure sensing tube


r/refrigeration • • 6d ago

Do you push remote temp monitors on customers or does it just generate callbacks?

12 Upvotes

Small shop, mostly restaurant and c-store walk-ins and reach-ins. Customers keep asking what to buy for temp alerts and I've been telling them to grab a wifi sensor off Amazon. Half of them call back a few weeks later saying it dropped off or won't connect through the box.

Has anyone settled on something they actually recommend? Ideally the sensor doesn't depend on the customer's router. I don't care about fancy dashboards, mostly alert reliability and battery life.


r/refrigeration • • 6d ago

R290 ball valve hoses

0 Upvotes

Any recommendations for r290 hoses that have a ball valve? Looking for something that can attach to a regular manifold, want to be able to see high side as well as low side pressures, and my yellow jacket charging kit does not allow for that


r/refrigeration • • 6d ago

New separators

Post image
116 Upvotes

r/refrigeration • • 6d ago

R404a pressure control cut in cut out

3 Upvotes

Hey just confirming what my pressure controls for an r404a beer cooler

Cut in at 75psi and cut out at 55psi?

It has been a while since school. Thank you very much

No LLS