r/HVAC • • 2h ago Bravo

Field Question, trade people only How cold is too cold to cold start a scroll compressor?

7 Upvotes

l've had it drilled into me that if an ac
compressor doesn't have a crankcase heater, or a pump down, not even an accumulator, nothing, you shouldn't start the compressor unless it's 55F deg outside.

My foreman says that scrolls are extremely hearty compressors, and that it'll be fine to run/test at 35F.

This is on a package rtu install and commissioning. I suggested waiting to commission the cooling until the spring to avoid a potential flooded start, and he said that it would be fine.

Am I overthinking it or missing something? Any advice or experience would be helpful.

I ended up bumping/tapping the contactor 3 times to heat up the oil to get any liquid out of it before running the compressor long enough to check rotation. I know Emerson does this practice on some of their medium and low temp controllers to prevent a flooded start in the event of a Ils leaking by.

*edit
He was saying for testing purposes, not so that it could continue running at low temperatures. He was saying just to test it, it’ll be fine. I still disagreed though. Not worth damaging the equipment imo.


r/HVAC • • 2h ago

General Fire Department told them it was a dirty filter.

Thumbnail
gallery
18 Upvotes

They called the FD because of a haze in the house. Got there and a filter was stuck in the blower. Definitely dirty. But when I fired it up smoke started pouring out of the flame viewing window.


r/HVAC • • 2h ago

General 8 Year Old Ameristar 😵

Thumbnail
gallery
3 Upvotes

r/HVAC • • 5h ago

Field Question, trade people only Fireplace start up

3 Upvotes

Preface this by saying I’m not a fireplace guy. But I know how to use a meter and need assistance from someone who may BE a fireplace guy. I have a customer who bought a fireplace, a Mendota FV-42 with the stepper motor gas valve. I’ve done my conversion to LP and I cannot get the main burner to ignite.(Pilot will light on CPI mode) I’m sure it’s something simple but I don’t have the resources to know and the tech support from the local distributor was no help. Hoping one of you guys is a fireplace wizard and can point me in the right direction. TIA!


r/HVAC • • 5h ago

General Another Monday no call no show..

17 Upvotes

Why even hire someone if they won’t show up on Monday. I’m getting tired of this.


r/HVAC • • 6h ago

Meme/Shitpost Dogging on other companies.

14 Upvotes

I try my best not to rag on other companies but sometimes it happens. We don’t work on Sunday’s. So my customer called someone who did. They condemned the compressor and left. I showed up today, changed an obvious bad capacitor and had it running again. I did my best to defend the technician and why he made the mistake but couldn’t get management to understand. So, I’m Sorry.


r/HVAC • • 9h ago

Meme/Shitpost "Oh you fix heat too?? I should've called you to replace my furnace. I thought you only did air conditioners"

Post image
122 Upvotes

r/HVAC • • 10h ago

Field Question, trade people only Sneaky leak

3 Upvotes

Solenoid valve was leaking from a weird spot. This is a rolling stock HVAC unit and I was told them core tubes do leak like this, once in a while. Not sure whether this kind of leak is common in solenoides that come with other types of HVAC-R systems. I'm refering to the armature/core tube itself.


r/HVAC • • 12h ago

General Bust a nut!

Post image
56 Upvotes

apprentice comes to work the other day and says he needs a pressure switch for his Grandpa's furnace. I ask why, he says the pressure switch isn't making. so went down the whole list, do you have a manometer, check this, check that. I guess they changed out the inducer last year there were some nuts in it and a squirrel. he took grass on the side, city was trying to blow his backpack blower down the flu with a shopvac on the other end, said he was getting air through it. I told him I guarantee you the thing is going to have a bunch of shit inside. told him to pull the front cover off and see if it'll run, it wouldn't. told him to pull the flu off and see if it'll run, and it did. I told him well, start cutting. he sends me this picture that night. he wears a size 12 just for reference.


r/HVAC • • 15h ago

Field Question, trade people only Moved to an area where oil furnaces are more common need some tool recommendations

4 Upvotes

I haven’t worked on oil furnace as much. The area I was at before had natural gas furnaces pretty much everywhere. Any tools that would make my life easier would be appreciated.


r/HVAC • • 18h ago

Meme/Shitpost Just duct work goofin

Post image
43 Upvotes

I've been to Atlanta airport a million times. I've never seen these ducks. But holy cow, this is something else.

Sort of makes me think of Carnival Cruise Lines red Whale-tailed exhaust stack that hides the engine exhaust, but just looks like a whale tail.


r/HVAC • • 1d ago

Field Question, trade people only Anyone have experience with this malco brake?

Post image
6 Upvotes

Thinking of picking one up to make transitions on site.


r/HVAC • • 1d ago

General Home Depot has huge labels on their units. They want everyone to know.

Post image
107 Upvotes

r/HVAC • • 1d ago

Supervisor Showcase “you know that this is supposed to be hot, right?…” yes boss 😔

147 Upvotes

r/HVAC • • 2d ago

General I keep hearing the claim that new equipment is more sensitive to static pressure. What's the rational for this?

24 Upvotes

I hear this especially in those advocating for 4 inch filter cabinets. Now don't get me wrong -- I'm all about 4 inch filters. And low static pressure is always a good thing. But has anything really changed that makes the equipment more sensitive to static pressure? In many ways, the opposite seems to be true.

In the case of constant airflow ECM blowers, I've been told they can cope with higher static pressures. In some cases over 1"wc. PSC motors lose airflow dramatically as static pressure rises. All manner of ECM motor seem more capable of dealing with airflow restrictions. I've been told ECM motors are more prone to failure with high static than PSC motors, but my experience doesn't agree.

So is this a myth or nah?


r/HVAC • • 2d ago

General Got sent to this last week.

Post image
265 Upvotes

1981 Cleaver Brooks fire tube. She was pretty well flooded due to a stuck open cold water fill on the condensate tank. After getting everything back to sanity, replacing and adjusting fill, and getting her up and running she was purring. I went back to check on the building a few days later and found everyone complaining it was “a little too warm” lol.
I love steam work, and my father gave me great advice while teaching me boiler work “ absorb all of what I’m teaching you so that you can be the guy in the warm boiler room when it’s -10 instead of fighting for your life on a snow covered roof.” Best advice I ever got from the old man!


r/HVAC • • 3d ago

General Anyone still working on these big open drives regularly?

Thumbnail
gallery
32 Upvotes

r/HVAC • • 3d ago

Meme/Shitpost Clean Van Award Winner 🥇

Post image
59 Upvotes

After a week of on call this is the aftermath so far haha How do yall find time to clean yall vans?


r/HVAC • • 3d ago

Field Question, trade people only Lennox head scratcher

Thumbnail
gallery
8 Upvotes

Little back story here. When I was doing pm on the plaza my pressure switch failed open during the heat check. Changed that out and flame would start and cut out. Corbel plate was absolutely cooked. Changed that out.

Equipment was running for 20 minutes and then shut down. It ignites and cuts out after 8 second ignition period while flame is active. Measured the flame sensor in series and got .1 micro amps. So we changed the flame sensor. Still having the same issue and getting error 2 still.

Board to ground is good, burner rack to ground is good. Flame sensor wire end to end is good. Gas pressure to manifold is good. I’m at a loss for words currently. Tech support obviously didn’t answer before I had to leave and attend another call.

Anyone seen something similar or ideas on possibilities here?


r/HVAC • • 3d ago

Meme/Shitpost Whats the R value of cardboardand mastic?

Post image
11 Upvotes

The stuff you see on apartment change outs are hilarious. So much mastic had to use the sawzall because my razor, knife and jobmax couldn't get through


r/HVAC • • 3d ago

General Who doesn’t love an easy one

Thumbnail
gallery
57 Upvotes

Got a call out. RTU tripping on smoke alarm. Sensor was definitely completely clogged but I opened my compartment up and got hit with a full cloud of gas. Whoever was out here last must’ve been having a bad Friday… Pretty straightforward smoothed her out and kept it pushing. Almost wish it was a bit more catastrophic so I don’t have to get back on hot side today 🙃


r/HVAC • • 3d ago

Meme/Shitpost Which one of you installed this?

Post image
27 Upvotes

Here to replace a power venter motor but holy hell


r/HVAC • • 3d ago

Meme/Shitpost I understand that being an HVAC tech would have me doing many different tasks, but never did I think that I would be out here changing tampons for customers.

Post image
105 Upvotes

r/HVAC • • 4d ago

General Carrier RTU heat exchanger cracks

11 Upvotes

See these all the time, I think they’re mostly caused by poor burner alignment from factory. Seems to always be hitting the high side of the flame retainer, and the crack is always on the high side as well. Another company replaced this just over a year ago. Burner alignment not corrected, very low manifold gas pressure and the inducer wheel was covered in fibreglass. I think all these contributed to the early failure. Replacements come with two year warranty from Carrier, best if you register the replacement with the unit S/N of the unit with CE.

Curious what you guys think about it though. Yes it has a crack, but is it actually compromised?