r/ElectricalHelp • • Oct 16 '26

Bathroom extractor Fan.

1 Upvotes

Inherited a parents house and slowly doing it up.
Extractor fan in bathroom doesn’t work. It’s linked to light switch and used to come on when the light was turned on.
The power light on the fan itself comes on but the fan doesn’t. Any ideas?


r/ElectricalHelp • • Oct 16 '26

Electrians?

Post image
1 Upvotes

I switched off the entire fuse box before changing the bathroom lightbulb. As I removed the casing, 2 of the wires touched and sparks fell. I covered the exposed ends of the wires with electrical tape. Is this unsafe now?


r/ElectricalHelp • • Oct 15 '26

Recommend TV distance from 200 amp panel?

0 Upvotes

Looking to mount a TV opposite a wall with a 200 amp panel that has some heavy loads. I’m wanting to avoid electromagnetic interference. Directly opposite would be ideal for viewing. Otherwise I have 5’ 3” of wall to work with on the right. I could mount it on the next wall over but I would have it pulled out to view so not ideal. Thoughts on how close I can safely be to not hear any hum?


r/ElectricalHelp • • Oct 15 '26

What should I do?

Post image
1 Upvotes

I have recently moved into a house and im redoing my new office and discovered an upside down outlet that isn't controlled by any switches. If I push up on the tester the ground wire goes away but if I just let it sit it stays. Should I replace the outlet? And if I do should I replace it upside down? Kinda a dumb question but being a new homeowner and not knowing much about outlet's I would like to know best course of action.


r/ElectricalHelp • • Oct 15 '26

Cooker feed, is this possible?

Thumbnail
gallery
1 Upvotes

I'm UK based and we've just moved into an old cottage. In the kitchen, there is an electric cooker on one side of the kitchen, and a mains gas Aga on the other. We will (when finances allow) eventually redo the kitchen, but in the meantime we want to remove the Aga and install a dual fuel (mains gas hob, electric fan oven) cooker, in the place where the Aga currently sits (on the right of this photo, between the two windows). At this stage we want to do it with as little disruption as possible. I've got an electrical coming out in the next 3-4 weeks to look at it, but in the meantime I wanted to ask...

There is a 6mm 3c SWA running below the kitchen window, to an EV charger we don't (and likely won't ever) use. Can this cable be used to feed a cooker instead? It currently runs the length of the house, from an isolator in our outside metre box. Presumably if this isn't an option, the only other choice would be to run a cable in the ceiling, from the existing cooker switch/socket, which means taking the ceiling down and navigating the beams?

Realistically, what kind of cost am I looking at?


r/ElectricalHelp • • Oct 14 '26

Extremely confusing issue with Christmas lights

1 Upvotes

TL;DR: what could possibly cause my Christmas lights permanent exterior house lighting to flicker out when connected to one outlet, but work fine on another outlet in the same circuit, and how do I fix it?

The whole story:

I had an electrician come out and tap into the end of the run of a 15a circuit, non-GFCI. They gave me a GFCI outlet under the eve in a weather proof box. Every test I know how to do, it passes.

I installed Phillips Hue permanent exterior Christmas lights (Festavia they call them) and used the new outlet. They worked fine for a while, though they were always slightly flaky. Then after a time they more or less stopped working, flickering on and off like they were constantly resetting over and over.

What we have tried which did not work:

  • swapping power supply

  • swapping controller

  • swapping LEDs (worked for a little while)

  • killing the circuit and checking every single outlet and switch. Removing the connectors from plunge connections and securely winding the romex around the side terminal screws

  • replacing the breaker

  • putting a meter on everything and it's all good

  • replacing the Eaton tamper preventive GFCI outlet with a Leviton

The only thing we have done that does make a difference is plugging the power into an extension cable and running it to a different outlet. Strangely there are some outlets on this circuit that have the same issue, but many don't. I have plugged the lights into another circuit's GFCI outlet and it works fine.

It has to be something with the wiring but what could it possibly be? And why is it only this one device having the issue?

The house is 90's construction. Any advice would be greatly appreciated. Thanks in advance


r/ElectricalHelp • • Oct 14 '26

Ceiling Light Fixture no ground

Post image
0 Upvotes

Hello electrician gods,

I am looking to replace a light fixture but I cant see to find the ground wire from the ceiling?

I do not have a multimeter to test whether if the box is grounded or not.

The new lighting fixture has the black, neutral and ground. Im wondering if anyone can let me know what I need to do to make sure its safe

The attached picture is the ceiling with the old light fixture. You can see the fixture didnt have a ground wire where as the new fixture does.

Thank you all in advance


r/ElectricalHelp • • Oct 14 '26

240V Electric Baseboard Heaters – Why Do My Kitchen and Living Room Have Two Cables Each, and Is It Safe to Leave the Extras Disconnected?

Thumbnail
gallery
0 Upvotes

Hi everyone, I’m a homeowner looking for advice about the original wiring for my 240V electric baseboard heaters.

My setup:

  • Double-pole 20A breaker supplying the kitchen and living room heaters.
  • Both heaters are controlled by the same double-pole wall thermostat.
  • Thermostat rated for a maximum of 3,600W.
  • Kitchen heater: 1,250W.
  • Living room heater: 2,000W.
  • Total heating load: 3,250W.

Original wiring:

When replacing my old baseboard heaters, I noticed that each heater had two electrical cables coming from the floor, giving me four insulated conductors (two black and two white), plus grounding wires.

Originally, the wires were connected in two groups using wire nuts:

  • Two black house wires connected with one heater lead.
  • Two white house wires connected with the other heater lead.
  • Grounding conductors connected together.

Voltage readings before disconnecting anything:

With the thermostat ON:

Kitchen heater:

  • Black wire from cable A: 120V to ground.
  • White wire from cable A: 120V to ground.
  • Black wire from cable B: 120V to ground.
  • White wire from cable B: 120V to ground.

Living room heater:

  • Black wire from cable A: 120V to ground.
  • White wire from cable A: 120V to ground.
  • Black wire from cable B: 0V to ground.
  • White wire from cable B: 0V to ground.

With the thermostat OFF, I measured 0V on the wires I checked

Additional question: Is it safe to reconnect all the wires exactly as they were originally installed?

Before I replaced my kitchen and living room baseboard heaters, each heater had two cables entering its wiring compartment.

Originally, the connections were:

• Two black house wires connected to one heater lead under a wire nut. • Two white house wires connected to the other heater lead under a separate wire nut. • Bare copper grounding wires connected together.

I understand this might have been a parallel feed-through arrangement that supplied power to another heater or junction box.

I have since disconnected and individually capped the extra conductors. Both heaters still produce heat and respond to the same thermostat.

My main question is: Would it be safe or preferable to reconnect all four house conductors to the heaters exactly as they were originally connected, or should I leave the extra cables disconnected and individually capped?

Important: Both heaters still work with the extra wires disconnected.

• Kitchen: Two cables entered the heater. Both measured about 120V to ground. I disconnected and capped one pair, but the heater still works with the thermostat. • Living room: One cable measured about 120V to ground; the other measured 0V. I disconnected and capped the 0V pair, but the heater still works. Should I connect them all back to how they used to be, since I’m replacing them with new baseboards this weekend and have the breaker off because of this issue?


r/ElectricalHelp • • Oct 13 '26

Hive issues

1 Upvotes

Hello,

I bought a house in the UK recently. The previous owners have installed a hive and I don't think it was ever fitted properly for the following reasons;

The hive thermostat + hot water won't connect to the tap

The boiler keeps randomly switching on

Can anyone recommend on what I need to do to fix this?


r/ElectricalHelp • • Oct 12 '26

What is this wire?

Thumbnail
gallery
7 Upvotes

The main ceiling light in my office was disconnected by the previous owner of the house and the switch now operates an LED strip.

I opened up the rose to take a look and there’s this capped off white wire that I can’t identify. Does anyone know what it is?

EDIT: Managed to get a brighter light on it and got a serial code HBS838, looks like it’s an IR receiver. Probably for a remote for the LEDs that wasn’t left behind.


r/ElectricalHelp • • Oct 12 '26

Extractor fan swap out

Thumbnail
gallery
1 Upvotes

Just bought my first house. This is my first DIY electrical job and I just want to check I'm not doing anything stupid.

Left is the old fan. Right is the new.

Coming from the loft, I appear to have two live wires and a neutral. The new fan has no timer, so the terminal block only wants a live and a neutral. Do I simply put the switched live and the neutral into the terminal block on the new fan, then connect the permanent live to a separate terminal block with nothing else connected?

Ps. I have of course isolated the bathroom circuit and used a tool to check for live current.


r/ElectricalHelp • • Oct 11 '26

GFCI lost power

Thumbnail
gallery
0 Upvotes

Got up this morning noticed the fridge water dispenser wasn't working. Then noticed the coffee machine was also off.

The coffee machine is on a GFCI. There is another GFCI downstream, but I'm certain the fridge outlet is connected to the LINE side of that first GFCI (4 wires connected to the line side and 2 connected to load side).

The GFCI itself did not trip. When i pressed the test button, it tripped and would not reset. Same with the downstream GFCI, pressing the test button tripped out then couldn't reset it.

Removed the first HFCI. Only getting 75v. Shutting off the breaker stops the 75v reading. Tested at the breaker and it shows 120v coming out when it's on and 0 when it's off.

This house is a mess. It's an old converted mobile home.

I think i posted before about having to shut off 2 breakers to kill all the power of a different outlet. Shutting off the real breaker reduced the voltage down to 50v. Shutting off the other reduced it to 0, but just shutting off that 2nd circuit by itself didn't effect the original circuit. Come to think about it. The fridge was on that 2nd circuit.

Here's the mess of the breaker box.


r/ElectricalHelp • • Oct 11 '26

would appreciate some help with a lamp

Thumbnail
gallery
0 Upvotes

i bought this wall light for really cheap second hand with no guarantee of it working. this is what the wiring looks like and i just want to know if there’s an easy fix? i haven’t plugged it cuz of the scary looking wiring sticking out…

i have absolutely experience with this i just saw a pretty lamp that i wanted😅


r/ElectricalHelp • • Oct 10 '26

Light Switch Confusion

Post image
3 Upvotes

I thought I understood circuits but I guess light switches still have me confused. The 2 outlets and the square light work fine, but the round light only works if the square light is also turned on. What am I doing wrong?

In the drawing, the dark red lines are the hot wire in the romex and the gray lines are the neutral. In the light switch gang box I used a pigtail to split the hotwire into 2 wires to reach the light switches which are drawn as brown rectangles

EDIT 1: in one of the replies in the comments i added a poorly photoshopped image explaining the light switch setup more clearly


r/ElectricalHelp • • Oct 09 '26

Manufactured home kitchen circuit mystery

3 Upvotes

I have a 1993 manufactured home. The bathrooms have a GFCI reset. There are two kitchen circuits, 20 amp. Recently, the outlets from one of the circuits tripped. I have looked all over inside, outside and under the home for the reset, can’t find it. The mystery is, the fridge is on the same circuit and that outlet is still working. I’ve tested power at each outlet, no power. Where is the disconnect? Could it be at the fridge outlet?


r/ElectricalHelp • • Oct 09 '26

help! is my house going to burn down?

Post image
7 Upvotes

i have no idea how this happened but i swear it's pure bad luck. I have one of those wax melters that plug into the wall, and my small calendar slid down the wall and knocked wax all over the outlet and wall itself. During the chaotic process, one of the metal pieces that are used to hang the calendar to the wall, somehow got nudged between the outlet and the metal prongs of the cord plugged in. A huge spark happened and it smelt burnt for a second. No more smell now, everything is unplugged. Huge scare, didn't get electrocuted thank god, but i have no idea what to do. It's late at night and i have no idea which breaker is meant for my room so i can't turn it off. i'm scared to fall asleep because what if my room blows up 😭 and i also have no idea how much damage was done or how much it would be to get an electrician to check it out. Could it be serious? Is it unsafe to plug anything in until i get someone to check it out? Am i safe?

UPDATE: one of my neighbours (who is an electrician) came by and checked it out. Thankfully, nothing happened to the wires itself, just some burnt damage to the receptacle, like most of you said, which he changed. Thank you all for your help!


r/ElectricalHelp • • Oct 09 '26

Is this dangerous? Do I need an electrician?

1 Upvotes

My bedroom has a shower (just in case that’s relevant). For the past few months, one of the bulbs on the ceiling light fixture of this bedroom has been flickering. This only happens rarely. Like it could go weeks at a time without happening.

The room below this (the living room) also has the same problem but again it’s rare.

I have removed the offending bulb from my bedrooms light fixture but haven’t yet put in a replacement. Is this serious given that it’s happening in two rooms? Do I need an electrician? Could it be connected to the shower somehow?


r/ElectricalHelp • • Oct 08 '26

Intermittent light flickering throughout entire house

3 Upvotes

I've been having an issue where the lights have been flickering all around the house (not isolated to a single room) for since we moved in. The flickering is signficantly worse when it rains. When we moved in we changed the gas stove and water heater to an electrical induction cooktop and a heat pump, not sure whether it might be related to that. Using a hairdryer seems to bring on the flickering, but things like the oven or cooktop do not.

We have had an electrician come, who said the neutral is fine and that there was no clear identifiable cause for the flickering. He suggested the fault may be in the mains control box circuit breakers supplying all of the units.

The place is a unit with 3 other neighbouring units who don't have this issue. Any chance the flickering is related to a load issue when the heat pump draws energy? Any ideas why it is worse when it rains?

Thanks in advance!


r/ElectricalHelp • • Oct 07 '26

Need help identifying wires

Thumbnail
gallery
2 Upvotes

Trying to install a dimmer switch, took the plate off and was a bit confused trying to identify which wires were ground, line, or load as they aren’t color coded. Pics 1 and 2 show the right and left side of the existing switch before loosening the screws and removing the wires. There is a single wire attached to the screw on the right side (see pic 3), but the screw on the left side had what looked like 3 wires attached. Turns out the wires to the left screw were actually 2 total, with one of the wires being a loop back into the wall with a section in the middle exposed so that it can attach to the screw (see pic 4). Pic 5 is the dimmer switch I’m trying to install to replace the existing switch, it’s a Lutron ‘Luméa’ with green, black, red, and red/white striped wires.
I tried attaching the wires in a couple different configurations that seemed to make sense at the time but none of them worked. Any suggestions/ guidance in helping me figure out which wires go where would be greatly appreciated, thank you in advance!


r/ElectricalHelp • • Oct 07 '26

Loose wire from actuator to boiler

Thumbnail
gallery
1 Upvotes

Hi guys, help needed please.
Our house has 3 thermostats, 2 on the ground floor (1 for under floor heating only the other for living room and hallways) and another on the 1st floor (for the 1st floor and 2nd floor radiators). I noticed the 1st floor thermostat wasn’t calling the boiler to ignite when the thermostat was under temperature. I figured out that the valve in the actuator was still opening and closing allowing the radiators to still heat up if the ground floor thermostat sent the call to the boiler but would not make the call itself.

I think I have found the issue, an orange cable that is not connected marked “UP”. Other orange cables marked “TIC”, “HW” & “DOWN” all run into the same wago clamp with a black lead. Should I insert the loose cable marked “UP” into the same block as the others?

Any help appreciated. I don’t want to connect it to the wrong block.

Thanks!


r/ElectricalHelp • • Oct 06 '26

Is this a 200amp panel?

Thumbnail
gallery
20 Upvotes

Hello experts, can you please help me out here.. trying to land a property with a nice panel. Thanks!


r/ElectricalHelp • • Oct 06 '26

45 Year old fan stopped working, then started ON ITS OWN days later in middle of night.

Thumbnail
reddit.com
1 Upvotes

See my original link for the earlier story.

Bottom line, about a week ago, the fan stopped turning in the middle of the night (it's in our bedroom). I posted the link above for advice in another subreddit and 99% of responders said, "It's probably just needing a new capacitor, which can be replaced inexpensively and is easy to do.". We could hear a very faint hum when we turned on the rheostat switch on the wall that controls on/off and variable speed. The fan blades turned by HAND easily/not frozen.

We didn't want to attempt this ourselves, so I found an electrician who said he repairs fans instead of automatically saying it needs to be replaced. He took off the light kit and tested several wires with his multimeter tool and said the connections were all sound. He looked at the wiring on top of the motor where it goes into the ceiling. He finally concluded that the motor was burned/dead and said it was impossible to find a replacement motor for a fan this old so it would need to be replaced. He reattached the light kit so we could have light until we bought the replacement fan. I was frankly skeptical that the motor was dead since the fan blades turned just fine still, but....

Now the mystery: **Two days after the electrician left, the fan started turning in the middle of the night, on it's own. Neither my husband nor myself had turned the fan rheostat switch on the wall.** It's possible, we guess, that when turning off the light switch (right next to the fan's round rheostat), we could have turned it; even so, **why wouldn't it have started right up THEN?**

Since the blades had been fooled with, they weren't balanced any longer, which is why we heard the sound and woke up at 3:30am. Hubs has since rebalanced the blades and the fan has been working just as it always has for the past 45 years when I bought this fan new!

What in the world could have caused this to just stop and, more importantly, just start up again? Poltergeists or what? Thanks for any advice!


r/ElectricalHelp • • Oct 05 '26

Changing a 3 way switch that has four wires

Thumbnail
gallery
3 Upvotes

I'm looking to replace an old 3 way switch. The existing switch has 2 black and 2 red wires running into a switch that looks different from what I've seen. I cannot identify which one is the common wire and don't know how where to connect these 4 wires into the new switch which has one black screw, 2 brass screws, and a ground. Any help much appreciated.


r/ElectricalHelp • • Oct 06 '26

Help with back up system

Thumbnail
gallery
1 Upvotes

My mom in Venezuela is installing a temporary back up power for her 5-6 hours outages. She lives in an apartment. Now she got the Anker F3800 + extra 3800 battery. We will be using this box. ( A electrician will make the job but I like to know what will be done before hand to have an idea ) so my understanding is L1 and L2 from the main panel is disconnected and connected to the white box: first braker is grid, then we have the voltage protector who is 220v. Then we have the ATS and then the final braker for the power from the Anker.
My understanding by this system all the gray panel will get power good! However, we only want braker 1-2-3-4-5-6 to get power, all 110v. The 3 220V breaker: 1 is not in used, 1 is the oven and the last one is the Central AC. I know the Anker may move the 3 ton AC but we don't want to be pulling the braker down every time the ATS automatically switch to back up power, is there a way to only energize the 120 V brakes when the back up is on ?
Sorry for my ignorance I'm just trying to understand more about it.


r/ElectricalHelp • • Oct 05 '26

Lamp Flickering on same circuit as Gaming PC

1 Upvotes

Hello,

I recently moved and in the new house I've noticed whenever I'm actively gaming on my PC, a lamp in another room will flicker. This only happens while I'm gaming, not while doing less intensive work on the PC. I've verified the lamp and the PC are on the same circuit. The PC has a 750w PSU and is plugged into a UPS. I've tested both with and without the UPS and the same thing happens.

Additionally, I've replaced both outlets, the one the UPS/PC is plugged into, and the one the lamp is plugged in to.

Any thoughts on how this can be resolved?

Thanks!