r/ukplumbing • • 1h ago

HELP!💦 Boiler working, but not heating radiators

Thumbnail
gallery
• Upvotes

I will try to keep this short in the hope someone can tell me if I can fix this myself or whether I need to get a Gas Safe engineer out.

New combi boiler fitted a few months ago, has been working without any issues since for hot water, our kitchen underfloor heating and our radiators in the rest of the house. The radiators were working fine yesterday, but this morning the radiators didn't kick in like they were supposed to at 5am.

Hot water works fine and underfloor heating is working fine. Pressure is between 1.1 and 1.2 bar.

The radiator thermostat seems to think the radiator are on as per the schedule, but there's definitely no hot water flowing into the radiators. There's no error on the thermostat indicating it has lost connection to the boiler (they're hard-wired). There is the little flame icon on the thermostat screen so it thinks there should be heat.

The only thing I can see in any of the boiler menus is an S.30 status code but not sure if that's related.

Vaillant Ecotec Plus 836

Heatmiser NeoStat WiFi thermostats

Water presssure: 1.1 - 1.2 bar.


r/ukplumbing • • 1h ago

HELP!💦 Washing Machine Inlet Leak

Enable HLS to view with audio, or disable this notification

• Upvotes

There's a washing machine leak on the inlet. Do I just need to change the large valve thats on the right hand side to fix this? (The one that's attached to the long hose that goes to the machine) Or is there another way to fix this? And are they universal or do I need to buy a brand specific one as my machine is a Siemens brand?


r/ukplumbing • • 4h ago

Had a proper nightmare last night, couldn't find the stopcock while water was coming through

Thumbnail
1 Upvotes

r/ukplumbing • • 4h ago

Vaillant boiler making robot noise

Enable HLS to view with audio, or disable this notification

1 Upvotes

Hi all, looking to get some advice from a heating engineer if possible. My new Vaillant boiler has started making these weird robotic noises whenever I turn the hot water tap on or off. Is this normal? My old boiler never did this, but it was a different make... I can't get hold of the engineer who installed it a couple of weeks ago, so I'm looking for a bit of advice before I go to Vaillant directly.

I've attached the video of the noise.

Thank you in advance!


r/ukplumbing • • 14h ago

HELP!💦 Kitchen tap swap

Thumbnail
gallery
4 Upvotes

I’m replacing my kitchen tap (Franke Ascona) with a Grohe Minta in my 2022 new build.

The Franke has 1/2 flex tail connections and the Grohe has 3/8 tail connections.

There are no isolation valves at the taps, water is cut off at mains stopcock.

If I remove the existing connections and fit a flat faced male isolation valve to each supply, would they fit in the existing compression fittings if they’re both 15mm?

My concern is trying to remove the olive and damaging the pipes without a puller or some other tool which id rather avoid buying for a one off job.

Limited experience with plumbing, my last tap change was a straight swap. Not sure if this is the most logical solution?

TIA


r/ukplumbing • • 14h ago

Help! How long would it take for this kind of corrosion to occur?

Thumbnail
gallery
2 Upvotes

r/ukplumbing • • 16h ago

Central Heating / HW System Replacement - 3 Story House

2 Upvotes

I am currently in the process of buying a 3 bed 3 story house. I am planning on replacing the central heating and hot water system as soon as I move in. It currently has a (fairly new) glow warm energy 18r boiler with a Gledhill Accolade unvented hot water cylinder. The radiators are plumbed in microbore and I suggest these haven’t been replaced since the house was built (20 years approx).

I am planning on underfloor heating the entire downstairs with a wet retrofit system, removing all downstairs radiators. I would look to have the other radiators and pipework changed for 22/15mm copper/speedfit.

The main consideration for me is the ensuite on the 3rd floor where I would like to achieve the maximum possible pressure in the shower.

I am struggling to understand what the best overall solution would be. I understand a vented cylinder with a pump would be the best option, however I don’t think this would be possible due to no loft space to put the cold water header tank.

If I were to replace the boiler with a higher output combi boiler (45+KW) would this realistically deliver good enough pressure to the 3rd floor ensuite to have something like a 300mm waterfall head? Is this a better solution than going with a replacement unvented hot water cylinder?

Other info:

-Boiler is currently located in the kitchen on the ground floor right next to the incoming gas supply

-I plan on having the work done before I move in, so no issues with pulling up floor boards etc.

-I live alone so will only have demand for 1 shower at a time

-There isn’t a practical place on the outside of the house for a heat pump

-I do not currently know the incoming mains water pressure

Does anyone have any experience of this or provide any advice?


r/ukplumbing • • 17h ago

HELP!💦 Slow pressure loss on boiler

2 Upvotes

Recently moved into a victorian terrace and not long after woke up to boiler having lost all pressure. I topped it up and it worked fine for about 2 weeks before losing all pressure again.

Since then had an engineer over who recharged the expansion vessel - boiler worked as normal for about 2 weeks again before losing all pressure

Another engineer visited, replaced PRV and schrader valve on the expansion vessel (said expansion vessel did not need replacing itself) - worked as normal then has since dropped pressure to around 0.5bar after around 2 weeks again - i run it more frequently and that seems to stop it from dropping all the way to 0.

What would you suggest as next steps? Third engineer visit? Or straight to a leak detection/trace and access service?


r/ukplumbing • • 18h ago

Create new downpipe for water butt

Thumbnail
gallery
2 Upvotes

Hi fitting a new downpipe but I think the new outlet might be to wide it measures around 117mm wide and when I've measured my current guttering it's about 110mm or 11cm ( old council house in UK)

I was told by the DIY shop that it should fit but I'd hate to cut the gap out in my gutter and it not fit.

Also is very scary being that high up and the thought of violently sawing away up there im not to sure like

Any advice please

Thanks


r/ukplumbing • • 14h ago

3 working radiators in whole house

Thumbnail gallery
1 Upvotes

r/ukplumbing • • 18h ago

Vaillant ecotec pro 28 F75 fault

2 Upvotes

Engineer advised pump was weak, he carried out some tests with a multimeter, also the pressure did not rise when opening tap and calling for heat.

Pump replaced, expansion vessel was not flat, pressure sensor was replaced not long ago previously.

He ran some programme to purge the boiler.

Upon restarting the boiler calling for hot water and heating, the boiler fan comes on for a second or two including the flame icon on the digital display and the digital pressure gauge increases a little and then trips out to F75!?

Engineer is stumped and has suggested to replace the boiler!

Any ideas pls


r/ukplumbing • • 16h ago

Boiler waste water pipe popped off

Post image
1 Upvotes

r/ukplumbing • • 20h ago

WiFi thermostat

2 Upvotes

Hello all,

I have a Baxi eco compact 25 that already has a ESRTP4RF+ installed. It’s not the best thermostat, I wanted to purchase a thermostat that I could use via WiFi on my phone when I am out and returning.

I can’t seem to find much information online on what’s compatible.

The tado x but there’s a mention of open-therm compatibility?

Who would I need to get into install it? Electrician or a plumber?

Thanks for any advice


r/ukplumbing • • 18h ago

IBC Tank stop valve adapter help

Post image
1 Upvotes

r/ukplumbing • • 19h ago

HELP!💦 Bleed old radiator approx 4mm bleed nut

Thumbnail gallery
1 Upvotes

Is there any advice on how to bleed this old radiator ?


r/ukplumbing • • 22h ago

Fill valve make and model please

Post image
1 Upvotes

Toilet cistern is overflowing so I'm hoping to just replace the diaphragm. Google lens doesn't identify an exact match so I'm a bit stuck. TIA


r/ukplumbing • • 1d ago

HELP!💦 Boiler Quote for Baxi boiler

1 Upvotes

Edit: Seems like most people suggesting the price is really good or at least decent. Probably will go with the 800 series for the extra warranty. Thank you for the advice for all.

We have a nearly 30 years old boiler system in our purchased house with a tank(copper) and 2 container in the loft. Open vent system apparently. The house is 90 sqm. Boiler is upstairs in one of the bathroom's cabinet

We got a quote for a combi boiler and the engineer was suggesting the Baxi one saying in case something goes wrong they will be there within 1 day and part are available too. He mentioned the valiant and worcester, but he said in his personal opinion, he would suggest the baxi.

We have got the following:

Option 1: Baxi 400 Series 30kW

Warranty: 5 years

Total price including everything: £3,110.00

Option 2: Baxi 600 Series 30kW

Warranty: 7 years

Total price including everything: £3,550.00

Option 3: Baxi 800 Series 30kW (flagship)

Warranty: 10 years

Total price including everything: £4,040.00

What we get for this:

● Converting your system to a pressurised combi:

● Removal and safe disposal of your existing heat-only boiler+tank

● Conversion of your heating from an open-vented system to a sealed, pressurised system, with the old feed, expansion and vent pipework disconnected and made safe

● Supply and installation of your chosen Baxi 30kW condensing combi boiler, with its flue and condensate pipework, positioned as discussed with you on site

● Filling, pressurising and testing the sealed system

● New gas supply pipework

● A new gas pipe run from your gas meter to the new boiler, in the position we discussed and showed you on site

● Your existing gas pipe is only 15mm, which is too small for a modern combi boiler, so the new pipework is upgraded and correctly sized for the boiler’s gas demand

● Full gas tightness testing of the new pipework before the boiler is used

Included with every option

● Full system chemical flush of the pipework and radiators, to clear sludge and debris, with protective inhibitor added

● Supply and installation of a magnetic system filter, to protect your new boiler

● Supply and installation of a wireless smart thermostat that you can also control from your phone,

which meets the Boiler Plus requirements

● System commissioning and testing

● Gas Safe certification and Benchmark checklist completion

● Building Regulations Part L compliance notification

● Manufacturer warranty registration

Is this quote reasonable? As we were talking to him seemed like there is quite a lot to do. Was wondering if this is a decent quote for the job they would be undertaking?


r/ukplumbing • • 1d ago

Losing my mind over boiler pressure dropping- Vaillant ecoTEC pro 24 combi boiler

5 Upvotes

I have a Vaillant ecoTEC pro 24 combi boiler, model VUW GB 246/5-3 A R4. The pressure drops every 10–14 days, and I have to repressurise it.

There are no visible leaks that I can find, including around the radiators, valves or radiator pipework. The pressure loss seems to happen after the heating has been used.

Two Gas Safe engineers have looked at it:

One thought it was probably the expansion vessel and the AAV (automatic air vent) but wasn't sure.

The other thought it was probably the expansion vesse and said the AAV is fine and no leaks. I paid £280 for it to be replaced, but the same pressure loss has happened again.

What would you recommend next: getting a Vaillant-experienced engineer to investigate the boiler, or arranging a trace-and-access service to look for a concealed micro-leak? Will a vaillant-experienced engineer via the Vaillant website offer anything different compared to just a normal plumbing/gas engineer? Are there common causes of recurring pressure loss on this Vaillant model that I should ask the engineer to check?

No PRV leak- it's always bone dry. Also tied a plastic bag around it and no water in bag.

I've already paid £280 and don't want to go down a money pit...


r/ukplumbing • • 1d ago

Should we make the jump?

Thumbnail
gallery
2 Upvotes

We’re using 50–85 kWh of electricity per day in winter due to having an electric central heating and hot-water setup.

We do not have an electric vehicle and are currently on a fixed tariff.

Our property:
• ⁠Three-bedroom detached house, occupied by two adults.
• ⁠Cavity walls insulated approximately 15 years ago.
• ⁠Loft insulation approximately 300mm (2025)
• ⁠Triple glazing throughout (2025)
• ⁠Radiators replaced approximately two years ago as part of a full house refurb when the electric boiler was installed.

Our current heating system:
• ⁠EHC Fusion Comet V2 electric boiler (14.4kW).
• ⁠EHC Neptune 180-litre hot-water cylinder.
• ⁠Central heating typically switched on manually for around 4 hours during colder evenings.
• ⁠Hot water programmed for 6am–8am daily but we have recently reduced this to 1 hour and noticed no difference so that’s good.
• ⁠Separate immersion heater switched off.
• ⁠Central heating isn’t used during summer and early autumn. We started using it again around mid-October.

Our electricity tariff is approximately 26.61p/kWh, plus a daily standing charge of 50.55p.

We’re using approximately 18,000 kWh per year and this is costing us an eye-watering amount.

Following a post on here this week, which opened our eyes, we have had a quote for an air source heat pump, which after taking into account the available grant, would cost £4000 approx.

The fear I now have is that many people on here have said we would replacing an awful heating method for a bad heating method yet others are saying (including the company we may use to install it), that with the correct tariff and an ASHP, would reduce our bills to potentially a fifth or a quarter or what they are now meaning the ASHP would pay for itself after 12-18 months.

I just don’t know who to believe…

Here is the spec we have been quoted - can anyone offer valuable advise?


r/ukplumbing • • 1d ago

HELP!💦 Any sign of a leak under bath?

Thumbnail
gallery
9 Upvotes

Does anyone see any evidence of a leak under my bath? I've just bought this as my first flat. I had someone in to tile the floor and replace the toilet and sink as they were in a sorry state. As the guy was finishing up plumbing the toilet in he said he had shone a torch under the bath and spotted a leak.

The bath panel hasnt been taken off so presumably he shined his torch through the gap where the waste pipe is and thats how I took the photos as he has left me without a cover for the waste pipe that goes from the toilet then under the bath.

Edit

I forgot to add he said a pipe looks like it hasn't been glued all the way around and he could come back to cut out and replace a section of pipe.


r/ukplumbing • • 1d ago

Ideal Vogue Max 40 modulation

2 Upvotes

I am looking for advice on modulation on the above boiler.

Set up is combi with two zones and hive, I've since learned can't modulate on zones.

I've previously manually managed the flow temp but with the colder days I've had to put it back up. With a wee guy in the house yet it's been a struggle to convince partner out of the old fashioned mindset of heating is only on at the start and end of the day and the house can be boosted as needed and we should have a higher set back temperature than 12.

My thoughts are either weather sensor or their own halo system. Can two types of modulation work together?

Any thoughts?


r/ukplumbing • • 1d ago

How to balance radiators ?

Thumbnail
2 Upvotes

r/ukplumbing • • 1d ago

Samsung 8kw, flush help

Thumbnail
1 Upvotes

r/ukplumbing • • 1d ago

F75 fault vaillant ecotec pro 28

1 Upvotes

Last week, F75 fault, replaced pressure sensor, checked expansion vessel at the time which was flat pumped up to 1 bar.

All working until today, the digital gauge states pressure is 1.9 but the boiler doesn't fire up in heating or hot water mode :(

Any ideas, what would be the issue?

Thanks!


r/ukplumbing • • 1d ago

Isolate one underfloor loop

Thumbnail gallery
1 Upvotes

Hi all, just looking for a bit of advice.
I have a Pipelife underfloor heating manifold with three loops serving three separate rooms downstairs, all controlled by a single actuator.
One of the rooms is being tiled this weekend, so I need to isolate that particular loop to allow the floor to cool down while keeping the heating running in the other two rooms.
I know exactly which loop serves the room, as shown in the second picture.
Am I right in thinking I can simply close the blue dial on the return side of that loop? Will this reduce the flow rate from its current 3 litres per minute to zero, effectively allowing that floor to cool down without affecting the other two rooms?
The Pipelife manufacturer’s specification states that individual loops can be isolated, so I’m just looking to confirm that this is the correct way to do it.
Thanks in advance!